C-TEC, CFP763, CFP Relay Output Card (8 Output Per Zone Relays)
CFP Relay output card (as per CFP762 + 8 output per zone relays)
This Relay Output Card is designed to mount inside the CFP Fire Alarm Panel. When connected, it provides the following isolated (voltage free) relay outputs which are directly controlled from the Panel.
Reset
Changes over during the Panel’s reset cycle. Stays in this state for at least one second after all other Outputs have normalised. Typically used for resetting Fire System devices such as beam detectors.
Fault
Changes over for any fault condition (unless the User has disabled the Panel’s Fault Output). This output is failsafe in that the relay is energised when there is no fault. If the power is completely removed from the Panel then the relay will change over to produce a fault signal.
Aux
Changes over when there is an Alarm Condition and any Delay has expired or been overridden (unless the User has disabled the Panel’s Aux. Output). Typically used for controlling Fire System devices such as door closers, ventilation shut down, etc.
Rem
Changes over when there is an Alarm Condition and any Delay has expired or been overridden (unless the User has disabled the Panel’s Remote Output). Typically used for connection to Remote signalling equipment.